Hole and notch limits for a 2x8 joist
A sawn-lumber 2x8 measures 7 1/4" deep, so the largest hole is 2 3/8" across, and it has to stay 2" clear of the top and bottom edges. Enter your own hole or notch below to check it.
- Largest hole diameter
- 2 3/8" (exact limit 2.416")
- Hole to the top edge and to the bottom edge, at least
- 2"
- Deepest notch in the span
- 1 1/8" (exact limit 1.208")
- Deepest notch at the end, over the bearing
- 1 3/4" (exact limit 1.812")
- Longest notch
- 2 3/8" (exact limit 2.416")
2021 IRC Section R502.8.1, for a solid sawn-lumber 2x8 that measures 7 1/4" deep, on a single span supported at both ends. Fractions are rounded down to the nearest 1/8". Notches are also barred from the middle third of the span. None of this applies to I-joists, trusses or LVL: follow the manufacturer.
Rule: 2021 IRC R502.8.1 · Tested against 22 worked examples, 4 printed in a published source · How this is worked out →
Questions people ask
How big of a hole can I drill in a floor joist?
Under the 2021 IRC (R502.8.1) the hole can be up to one-third of the actual depth of a sawn-lumber joist, and its rim cannot come closer than 2" to the top or bottom edge. Rounded down to the nearest eighth, that is 2 3/8" for a 2×8, 3" for a 2×10 and 3 3/4" for a 2×12. On a 2×6 the edge rule governs and leaves room for a 1 1/2" hole.
Can I notch a 2×10 floor joist?
Yes, within limits. A notch can be no deeper than one-sixth of the depth (1 1/2" on a 2×10, rounded down), no longer than one-third of the depth (3"), and it cannot be in the middle third of the span. A notch at the very end of the joist, over its bearing, can be up to one-fourth of the depth (2 1/4").
How far apart do holes in a joist have to be?
The code says a hole cannot be closer than 2" to any other hole in the member, and where the member is notched, not closer than 2" to the notch.
Do these rules apply to I-joists, LVL or floor trusses?
No. Section R502.8.2 prohibits cuts, notches and holes in trusses, structural composite lumber, glued-laminated members, cross-laminated timber and I-joists unless the manufacturer’s recommendations permit them or a registered design professional has considered them in the design. Use the manufacturer’s hole chart for those products.
What if a joist has already been cut more than the code allows?
ICC’s CodeNotes says a structural member modified beyond what the code permits must be replaced with an unmodified member, or have a structural analysis done, usually by a registered design professional, to confirm it still has the required capacity.